Skip to main content
WIRES • CABLES • ELECTRICAL FITTINGS & ACCESSORIESBULK & CONTRACTOR PRICING:+234 814 479 6897Ibeju-Lekki, Lagos
Cable Sizing2 September 20267 min readBy Blac Rabbit Technical Desk

How to Choose the Right Electrical Cable Size (mm²) for Buildings in Nigeria

A practical reference for matching 1.5mm², 2.5mm², 4.0mm², 6.0mm² and 10mm²–16mm² copper conductors to lighting, 13A sockets, air conditioners, water heaters, cookers and generator feeds.

Close-up of multi-core copper electrical cable coils

Why Cable Size Matters

A cable that's too small for the load it carries overheats. The insulation degrades faster, the voltage dropping along the run gets worse the further it travels, and in the worst case the cable becomes a fire risk long before the breaker ever trips. Oversizing wastes money on copper you don't need. The goal is matching the conductor to the actual circuit load — not guessing.

The chart below is a general-purpose starting point for the circuits most Nigerian homes and small commercial buildings actually have. It assumes a reasonably short cable run (under about 25 metres) at normal ambient temperature.

Quick Reference: Cable Size by Circuit Type

Circuit / ApplianceRecommended SizeCable TypeTypical Breaker
Lighting points & ceiling fans1.5mm²Single-Core PVC (in conduit)6A
13A sockets & ring mains2.5mm²Flat Twin & Earth20A
Split-unit air conditioners (1–2HP)4.0mm²Flat Twin & Earth32A
Water heaters / instant showers4.0mm²–6.0mm²Flat Twin & Earth32A–40A
Electric cookers6.0mm²Flat Twin & Earth40A
Sub-main feed (meter to DB)10mm²Armoured SWA63A
Generator changeover feed16mm²Armoured SWA63A

A Note on Cable Run Length

The chart above assumes a short run. The longer the cable has to travel from the distribution board to the appliance, the more voltage it loses along the way — this is voltage drop, and it gets worse with distance and with higher current. For runs beyond about 25 metres (a detached boys' quarters, an outbuilding, a long generator feed trench), size up one step from what the table shows, even if the load itself hasn't changed.

Trade note: This chart is a general planning reference, not a substitute for a proper load calculation. Always have your final circuit sizing checked by a qualified electrician before wiring a building.